In this study; Thermal insulation applications in buildings and legal regulations on the subject were compiled, the ratio of thermal insulation applications in school buildings has been examined. The study aims to determine the ratio of thermal insulation applications to total cost and period of redemption in school projects. In the study, two school buildings were evaluated with 12 and 24 classrooms, which were completed and opened to the service in the central districts of Antalya. The thermal insulation details and manufacturing recipes for these buildings are presented. The total cost and insulation cost was prepared with AMP software which is the cost preparation program. Moreover, thermal dissipation in school buildings was calculated with the help of Carrier HAP 4.4. According to these values, annual operating costs were achieved. The period of redemption of thermal insulation productions were determined using the data obtained. As a result of the study; the ratio of thermal insulation applications to the total cost of building was calculated as 3.5% and period of redemption was calculated as 80 and 124 months, respectively, for school buildings with 12 and 24 classrooms.
Primary Language | Turkish |
---|---|
Journal Section | Articles |
Authors | |
Publication Date | June 30, 2018 |
Published in Issue | Year 2018 Volume: 33 Issue: 2 |