this study, condensation and vapor diffusion caused by different positioned
insulation in the wall for Mardin province were analyzed. In the analysis,
according to 2008 standard of TS 825, Glaser graphing method and graphical user
interface (GUI) were used in MATLAB. Extruded polyurethane foam was used as the
insulation material and normal unreinforced concrete was selected as the wall.
Evaporation and condensation amounts were determined by creating 6 different
wall models with the same insulation thickness of 20 cm thick and unreinforced
concrete wall covered with 2 cm plaster on the inside and 3 cm thickness on the
outside. The data obtained for 2 cm and 4 cm insulation thicknesses are
presented in tables and the results are interpreted for Mardin province. As a
result, it was seen that the worst wall structure in terms of condensation and
evaporation was obtained in the middle insulated wall and later in the interior
insulated wall structure. The externally insulated wall showed no condensation.
Condensation and vapor diffusion Glaser graphic method TS 825 Standard Insulation